Type EM-LON

LonWorks interface for EASYLAB controllers and adapter modules

Expansion module for EASYLAB fume cupboard controllers, room controllers, extract air controllers, supply air controllers, and adapter modules, for the integration of rooms or individual volume flow controllers with the central BMS

  • LonWorks FTT-10A interface
  • Communication only using standard network variables (SNVT)
  • The expansion module is fitted into the casing with the EASYLAB base component
  • Easy retrofitting
  • Double-stack terminal blocks for the LonWorks network
  • Service pin push button and corresponding indicator light


Interface to central BMS

  • When used on a controller with active room management function (RMF) the module provides also data points for the entire room, e.g. for total volume flows or consolidated alarms
  • When used on a single controller: data points for volume flow rate, alarm, damper blade position, or others
  • Centralised operating mode default setting, e.g. night-time operation

Expansion module LON FTT 10 00137415_0


  • Application
  • Description

Application

  • Expansion module Type EM-LON for the EASYLAB system
  • LonWorks FTT-10A interface to the central BMS
  • Data points for individual controllers or for the room
  • Room interface: Default setting of room operating modes within the EASYLAB system, increase or reduction of the air change rate, readout of the actual room operating values or evaluated damper blade positions, consolidated alarms
  • Controller interface: Operating mode default setting for a single fume cupboard controller, readout of individual operating values such as volume flow rates for single controllers, or individual alarms
  • Can be used with fume cupboard, supply air, extract air or differential pressure controller EASYLAB TCU3 and with adapter module TAM
  • For use in laboratories, clean rooms in the pharmaceutical and semiconductor industries, operating theatres, intensive care units, and offices with very demanding control requirements
  • Factory mounted or for retrofitting into the EASYLAB base component casing

Special characteristics

  • LonWorks free topology network with an arbitrary number of branches (star, line, and arbitrary combinations)
  • Communication only using standard network variables (SNVT)
  • Data interface for an EASYLAB controller or for an EASYLAB room with different functional profiles
  • System integration (binding) into the LonWorks network is required

Parts and characteristics

  • Microprocessor with basis programme stored in nonvolatile memory to load LonWorks applications
  • LonWorks transceiver FTT-10A – free topology – twisted pair
  • Double stack terminal block for LonWorks network (simple wiring)
  • Service pin push button and corresponding indicator light for sending the Neuron ID required for system integration
  • Two indicator lights to indicate 'sending data' and 'receiving data'

Construction features

  • PCB dimensions and fixing points correspond to the EASYLAB main PCB and the casing
  • Fixing with screws
  • Pin header to connect the module to the main PCB of the TCU3 or TAM

Technical information

Function, Technical data, Specification text, Order code, Related products

  • Function
  • Technical data
  • Specification text
  • Order code
EM-LON 00131144_0
① Plug base for connection with the EASYLAB main PCB
② Terminals for the LonWorks network
③ Service pin push button and corresponding indicator light
④ Indicator lights – data transfer


The expansion module EM-LON supplements the EASYLAB base components (controller TCU3 or adapter module TAM) with a LonWorks interface to link rooms or individual volume flow controllers to the central BMS.

The LonWorks interface supports the EASYLAB room operating mode concept. It is possible to set operating mode defaults in order to control different volume flow rates for daytime and night-time operation; it is also possible to increase or reduce the air change rate by a certain amount (volume flow rate setpoint change), e.g. to influence the room temperature.

Using the LonWorks interface, an individual alarm management system can be set up by consolidating configurable EASYLAB alarms. The interface also enables the transfer of actual operating values such as volume flow rates and damper blade position for a controller or for all controllers in a room.

Supply voltage

5 V DC from controller or adapter module

Communication interface

LonWorks-Transceiver FTT-10A, free topology, twisted pair

Connection to LonWorks network

6 terminals for cable cross sections of 0.12 – 1.5 mm² (LON A, LON B and screen, two of each)

Operating temperature

0 – 50 °C

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

EC conformity

EMC to 2004/108/EU, low voltage to 2006/95/EU

Dimensions (B × H × T)

78 × 65 × 100 mm


Expansion module to supplement an EASYLAB base component (controller TCU3 or adapter module TAM) with a LonWorks interface to link rooms or individual volume flow controllers to the central BMS.

The expansion module includes a LonWorks transceiver FTT-10A (free topology, twisted pair), a service pin push button for LonWorks integration, and indicator lights for 'sending data' and 'receiving data'.

Special characteristics

  • LonWorks free topology network with an arbitrary number of branches (star, line, and arbitrary combinations)
  • Communication only using standard network variables (SNVT)
  • Data interface for an EASYLAB controller or for an EASYLAB room with different functional profiles
  • System integration (binding) into the LonWorks network is required

Technical data

  • Communication: LonWorks-Transceiver FTT-10A, free topology, twisted pair
  • Connection to LonWorks using the double-stack terminal blocks

Data points for a single controller

  • Volume flow rate actual and setpoint values
  • Damper blade position
  • Operating mode
  • Alarm/status messages
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs

Additional data points for a fume cupboard controller

  • Operating mode default setting for the fume cupboard controller equipped with the expansion module
  • Selection of priority for operating mode default setting
  • Face velocity actual value and setpoint value (only for fume cupboard controllers with face velocity transducer, equipment function FH-VS)

Data points for an EASYLAB room

  • Operating mode default setting for the room: Just one data point is required to set the default operating mode for all controllers in a room
  • Selection of priority for operating mode default setting (central BMS or room)
  • Room operating mode
  • Volume flow rate setpoint change (by the central BMS, for example) for an external temperature or differential pressure control
  • Setpoint value switching for differential pressure control: Switching between two differential pressure setpoint values
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Room differential pressure actual and setpoint values
  • Room pressure alarm
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs
  • Configurable consolidated alarm (operating statuses, hardware faults)
  • Control input signal for sun protection/blinds (to be provided by others)

  • Any attachments are to be defined with the order code of the VAV terminal unit.
  • Retrofit possible

 

Single controller, EASYLAB room, LonWorks interface, Product details

  • Single controller
  • EASYLAB room
  • LonWorks interface
  • Product details
LonWorks, BACnet or Modbus interface on a single controller, e.g. fume cupboad controller 00183220_0
BMS central building management system
RMF Controller with active room management function
ROM Room operating mode, from the room control panel
IOM Individual operating mode, transmitted via BACnet or Modbus interface


Single controller

Interface for one EASYLAB controller

  • Local data interface for a fume cupboard controller, supply air controller, extract air controller, or adapter module TAM


Data points for a single controller

  • Volume flow rate actual and setpoint values
  • Damper blade position
  • Operating mode
  • Alarm/status messages
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs


Additional data points for a fume cupboard controller

  • Operating mode default setting for the fume cupboard controller equipped with the expansion module
  • Selection of priority for operating mode default setting
  • Face velocity actual value and setpoint value (only for fume cupboard controllers with face velocity transducer, equipment function FH-VS)

LonWorks, BACnet or Modbus interface for an EASYLAB room, e.g. on a room controller with active room management function 00183226_0
BMS central building management system
RMF Controller with active room management function
ROM Room operating mode, from the controller with room management function


EASYLAB room

Interface for one EASYLAB room

  • Local data interface for a TCU3 room controller (supply air or extract air) or TAM adapter module with active room management function
  • Room management function reduces the required number of network data points and hence the commissioning costs
  • Transmission of local data for the single controller and for the room


Data points for an EASYLAB room controller

  • Operating mode default setting for the room: Just one data point is required to set the default operating mode for all controllers in a room
  • Selection of priority for operating mode default setting (central BMS or room)
  • Room operating mode
  • Volume flow rate setpoint change (by the central BMS, for example) for an external temperature or differential pressure control
  • Setpoint value switching for differential pressure control: Switching between two differential pressure setpoint values
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Room differential pressure actual and setpoint values
  • Room pressure alarm
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs
  • Configurable consolidated alarm (operating statuses, hardware faults)
  • Control input signal for sun protection/blinds (to be provided by others)

Virtual function block 00261774_0


LonWorks interface

Description of network variables (SNVT)

All variables and parameters are based on standard network variables (SNVT); this ensures integration of the expansion module EM-LON into a LonWorks network.

The equipment functions that support each variable are listed under the special information for that network variable.

Abbreviations

  • FH: Fume cupboard controller
  • EC/SC: Extract air controller / supply air controller
  • RR: Room controller for supply air or extract air
  • TAM: Adapter module
  • RR-RMF: Room controller with active room management function
  • TAM-RMF: Adapter module with active room management function

Operating mode default setting

  • Input variables nviManOverride (SNVT_hvac_overid), nviOccCmd (SNVT_occupancy) and nviMode (SNVT_state) are available for operating modes
  • nviManOverride has the highest LON priority
  • nviMode has the lowest LON priority.
  • A configuration of the assignment is possible only for nviOccCmd by means of the parameter nciConfig_Occ (SCPTdirection).
  • The valid binding of an input variable results in a valid operating mode default setting in LON for a single controller or for the room
  • The invalid binding of an input variable does not result in an operating mode default setting in LON

Operating modes Standard mode

Standard mode means normal operation in the daytime (in Germany: usually according to DIN 1946, part 7, 25 m³/h extract air per m² main useful floor area)


Reduced operation

Low mode in comparison to standard mode, e.g. as a night-time setback


Increased operation

High mode in comparison to standard mode, e.g. in an emergency


Shut-off mode

Shut-off of the volume flow controller, e.g. to save energy at night or to shut down the system


OPEN position

Open position of the volume flow controller

Overview of input variables for LonWorks interface EM-LON

Variable Data type Unit Meaning
Variable Data type TCU3 TAM Meaning
Variable Data type Available with equipment function Meaning
Variable Data type FH RR RR RMF EC, SC TAM TAM RMF Meaning

nviManOverride

SNVT_hvac_overid


x



x

Operating mode default setting for controller or room

nviMode

SNVT_state


x



x

Operating mode default setting for controller or room

nviOccCmd

SNVT_occupancy


x



x

Operating mode default setting for controller or room

nviManOP_Disable

SNVT_switch


x



x

Enabling/disabling manual control

nviVolOffset_T

SNVT_switch



x



x

Signalling of a volume flow rate setpoint change for temperature control

nviVolOffset_P

SNVT_switch



x



x

Signalling of a volume flow rate setpoint change for differential pressure control

nviPressSetSel

SNVT_switch



x



x

Switching between differential pressure setpoint values 1 and 2

nviSunblinder

SNVT_switch



x



x

Control input signal for sun protection/blinds

nviVolflowExh

SNVT_flow

x

x

x


x

x

Connection of an extract air flow

nviVolflowSup

SNVT_flow

x

x

x


x

x

Connection of a supply air flow

nviSC_LockHP

SNVT_switch







Close and lock sash, high priority

nviSC_SetPos

SNVT_switch







Default setting from central BMS: Close sash

nviDO_Set

SNVT_state

x

x

x

x

x

x

Signalling to relays which are not used by the control system

nviVolflowSet_R

SNVT_flow







Default setting of volume flow rate setpoint (room), only for standard mode

nviPressSet

SNVT_press_p







Local default setting of room pressure or duct pressure setpoint value

nviVoltageAO2

SNVT_volt

x

x

x

x

x

x

Default setting of voltage for output AO2

1 only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Overview of output variables for LonWorks interface EM-LON

Variable Data type Unit Meaning
Variable Data type TCU3 TAM Meaning
Variable Data type Available with equipment function Meaning
Variable Data type FH RR RR RMF EC, SC TAM TAM RMF Meaning

nvoManOverride

SNVT_hvac_overid

x

x

x

x



Operating mode for a single controller

nvoManOverride_R

SNVT_hvac_overid



x



x

Operating mode for the room

nvoMode

SNVT_state

x

x

x

x



Operating mode for a single controller

nvoMode_R

SNVT_state



x



x

Operating mode for the room

nvoOccCmd

SNVT_occupancy

x

x

x

x



Operating mode for a single controller

nvoOccCmd_R

SNVT_occupancy



x



x

Operating mode for the room

nvoVolflowSet

SNVT_flow

x

x

x

x



Volume flow rate setpoint value for the controller

nvoVolflowAct

SNVT_flow

x

x

x

x



Volume flow rate actual value for the controller

nvoVolTotalExh

SNVT_flow

x

x

x

x

x

x

Total extract air for the room

nvoVolTotalSup

SNVT_flow

x

x

x

x

x

x

Total supply air for the room

nvoPressSet

SNVT_press_p



x



x

Differential pressure setpoint value for the room

nvoPressAct

SNVT_press_p



x



x

Differential pressure actual value for the room

nvoLocalAlarm

SNVT_switch

x

x

x

x

x

x

Alarm for the single controller

nvoSummaryAlarm

SNVT_switch



x



x

Consolidated alarm for the room

nvoPressAlarm

SNVT_switch



x



x

Differential pressure alarm

nvoVelocitySet

SNVT_speed_mil

x






Face velocity actual value

nvoVelocityAct

SNVT_speed_mil

x






Face velocity setpoint value

nvoSwitchPos

SNVT_count

x






Sash position (stage 1,2,3)

nvoWireSensorPos

SNVT_switch

x






Sash position (sash opening %)

nvoDampPos

SNVT_switch

x

x

x

x



Damper blade position of single controller

nvoSystemDevices

SNVT_count

x

x

x

x

x

x

Number of EASYLAB controllers

nvoStateDIO

SNVT_state

x

x

x

x

x

x

State of the digital inputs and outputs (TCU3)

nvoSC_LockHP

SNVT_switch







Feedback, sash has been locked, high priority

nvoSC_GetPos

SNVT_switch







Signalling of position status

nvoSC_Alarm

SNVT_switch







Signal for automatic sash device

nvoDO_SetByLocal

SNVT_state

x

x

x

x

x

x

Indicates which relay is already being used by the controller

nvoVoltageAI2

SNVT_volt

x

x

x

x

x

x

Actual voltage at input AI2

nvoVoltageAI3

SNVT_volt

x

x

x

x

x

x

Actual voltage at input AI3

nvoDampPosMax_FH

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position for fume cupboards – max

nvoDampPosMin_FH

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position for fume cupboards – min

nvoDampPosMax_RE

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position, extract air – max

nvoDampPosMin_RE

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position, extract air – min

nvoDampPosMax_TE

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position, total extract air – max

nvoDampPosMin_TE

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position, total extract air – min

nvoDampPosMax_RS

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position, supply air – max

nvoDampPosMin_RS

SNVT_switch

x

x

x

x

x

x

Evaluated damper blade position, supply air – min

nvoDampPosMax_EC

SNVT_switch

x

x

x

x

x

x

Output of the damper blade position of the extract air controller with the widest open damper blade

nvoDampPosMin_EC

SNVT_switch

x

x

x

x

x

x

Output of the damper blade position of the extract air controller with the least wide open damper blade

nvoDampPosMax_SC

SNVT_switch

x

x

x

x

x

x

Output of the damper blade position of the supply air controller with the widest open damper blade

nvoDampPosMin_SC

SNVT_switch

x

x

x

x

x

x

Output of the damper blade position of the supply air controller with the least wide open damper blade

nvoDampPosMax_TS

SNVT_switch

x

x

x

x

x

x

Output of the damper blade position of the supply air controller with the widest open damper blade

nvoDampPosMin_TS

SNVT_switch

x

x

x

x

x

x

Output of the damper blade position of the supply air controller with the least wide open damper blade

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Configuration parameter

nciConfig_Occ

Type: SCPTdirection

Equipment functions: FH, RR with RMF, TAM with RMF


Function

  • Assignment of SNVT_occupancy functional values to controller or room operating modes
  • SNVT_occupancy used for operating mode default setting for a controller or a room
  • nviOccCmd and nvoOccCmd are of Type SNVT_occupancy

nciMaxSendTime

Type: SCPTmaxSndT

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Minimum updating interval for the LON output variables when the value of the variables remains unchanged.

Input variables

nviManOverride

Type: SNVT_hvac_overid

Equipment functions: FH, RR with RMF, TAM with RMF


Function

  • SNVT_hvac_overid functional values for operating mode default setting
  • FH: Operating mode default setting for a single fume cupboard controller, only with individual operating mode default setting (stand-alone operation)
  • RMF: Operating mode default setting for the entire EASYLAB room

nviOccCmd

Type: SNVT_occupancy

Equipment functions: FH, RR with RMF, TAM with RMF


Function

  • SNVT_occupancy functional value for operating mode default setting
  • FH: Operating mode default setting for a single fume cupboard controller, only with individual operating mode default setting (stand-alone operation)
  • RMF: Operating mode default setting for the entire EASYLAB room

The assigment of functional values to operating modes is stored in the nciConfig_Occ table in the controller and can be configured

nviMode

Type: SNVT_state

Equipment functions: FH, RR with RMF, TAM with RMF


Function

  • SNVT_state functional value for operating mode default setting
  • FH: Operating mode default setting for a single fume cupboard controller, only with individual operating mode default setting (stand-alone operation)
  • RMF: Operating mode default setting for the entire EASYLAB room

nviManOp_Disable

Type: SNVT_switch

Equipment functions: FH, RR with RMF, TAM with RMF


Function

  • Upon enabling manual control the corresponding symbol appears on the fume cupboard or room control panels
  • For further information on manual control please refer to the EASYLAB design manual.
  • The variable includes the 'value' and 'state' fields but only the 'state' field is used.

nviVolOffset_T

Type: SNVT_switch

Equipment functions: RR with RMF, TAM with RMF


Function

  • Signalling of an external volume flow rate setpoint change, e.g. for adjusting the room air change rate or for external temperature control
  • The change signal is transferred as a percentage value of a volume flow rate change range that has been configured in the controller
  • The variable includes the 'value' and 'state' fields but only the 'value' field is used
  • Depending on the room configuration, several controllers will assume the setpoint change function

nviVolOffset_P

Type: SNVT_switch

Equipment functions: RR with RMF, TAM with RMF


Function

  • Signalling of a flow rate setpoint change for external differential pressure control
  • The change signal is transferred as a percentage value of a volume flow rate change range that has been configured in the controller
  • The variable includes the 'value' and 'state' fields but only the 'value' field is used

nviPressSetSel

Type: SNVT_switch

Equipment functions: RR with RMF, TAM with RMF


Function

  • If room pressure control of the EASYLAB system is active, this is the input for switching between two differential pressure setpoint values that are stored in the room management function
  • The variable includes the 'value' and 'state' fields

nviSunblinder

Type: SNVT_switch

Equipment functions: RR with RMF, TAM with RMF

from firmware version EM-LON 2.0 and TCU3, TAM 3.0


Function

  • Control input signal for sun protection/blinds, connected to the controller or adapter module
  • Switch outputs DO5 and DO6 will be used
  • This LonWorks default overrides any other defaults from the local room control panel

nviVolflowExh

Type: SNVT_flow, unit l/s

Equipment functions: FH, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 2.0 and TCU3, TAM 3.0


Function

  • Integration of an extract air flow into the room balance of the EASYLAB system
  • This default volume flow is considered for all volume flow calculations (balance and setpoint values)

nviVolflowSup

Type: SNVT_flow, unit l/s

Equipment functions: FH, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 2.0 and TCU3, TAM 3.0


Function

  • Integration of a supply air flow into the room balance of the EASYLAB system
  • This default volume flow is considered for all volume flow calculations (balance and setpoint values)

nviSC_LockHP

Type: SNVT_switch


Function

  • Control of an automatic sash device, high priority

nviSC_SetPos

Type: SNVT_switch


Function

  • Control of an automatic sash device

nviDO_Set

Type: SNVT_State

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 5.0


Function

  • Signalling to digital outputs (relay) that are not used by the control system

nviVolflowSet_R

Typ: SNVT_flow


Function

  • Default setting of volume flow rate setpoint (room), only for standard mode

nviPressSet

Typ: SNVT_flow


Function

  • Local default setting of room pressure or duct pressure setpoint value

nviVoltageAO2

Type: SNVT_volt, unit V

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 4.0 and TCU3, TAM 7.0


Function

  • Default setting of voltage for analogue output AO2
  • 0 – 10 V DC, in increments of 0.1 V

Output variables

nvoManOverride

Type: SNVT_hvac_overid

Equipment functions: FH, EC/SC, RR, RR with RMF


Function

  • Output of the operating mode for the volume flow controller

nvoManOverride_R

Type: SNVT_hvac_overid

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of the room operating mode

nvoMode

Type: SNVT_state

Equipment functions: FH, EC/SC, RR, RR with RMF


Function

  • Output of the operating mode for the volume flow controller

nvoMode_R

Type: SNVT_state

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of the room operating mode

nvoOccCmd

Type: SNVT_occupancy

Equipment functions: FH, EC/SC, RR, RR with RMF


Function

  • Output of the operating mode of the volume flow controller


The assigment of functional values to operating modes is stored in a table in the controller and can be configured.

The table for the assignment of functional values of SNVT_occupancy in controller or room operating modes can be adapted by means of nciConfig_Occ.

nvoOccCmd_R

Type: SNVT_occupancy

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of the room operating mode


The assigment of functional values to operating modes is stored in a table in the controller and can be configured.

The table for the assignment of SNVT_occupancy functional values to room operating modes can be adapted using the configuration parameter nciConfig_Occ.

nvoVolflowAct

Type: SNVT_flow, unit: l/s

Equipment functions: FH, EC/SC, RR, RR with RMF


Function

  • Output of the volume flow rate actual value of the volume flow controller

nvoVolflowSet

Type: SNVT_flow, unit: l/s

Equipment functions: FH, EC/SC, RR, RR with RMF


Function

  • Output of the volume flow rate setpoint value of the volume flow controller

nvoVolTotalExh

Type: SNVT_flow, unit: l/s

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the total extract air volume flow rate of an EASYLAB room
  • This includes the extract air volume flow rates of all fume cupboards and extract air contollers as well as the additional extract air volume flow rates (constant and variable) from other controllers.

nvoVolTotalSup

Type: SNVT_flow, unit: l/s

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the total supply air flow rate of an EASYLAB room
  • This includes the supply air volume flow rates of all supply air controllers as well as the additional supply air volume flow rates (constant and variable)

nvoVelocityAct

Type: SNVT_speed_mil, unit: m/s

Equipment function: FH


Function

  • Output of the face velocity actual value if the fume cupboard controller is equipped with a face velocity transducer (FH-VS)

nvoVelocitySet

Type: SNVT_speed_mil, unit: m/s

Equipment function: FH


Function

  • Output of the face velocity setpoint value if the fume cupboard controller is equipped with a face velocity transducer (FH-VS)

nvoWireSensorPos

Type: SNVT_switch

Equipment function: FH


Function

  • Output of sash position of the fume cupboard as a percentage value between closed position (0 %) and open position (100 %) if the fume cupboard controller is equipped with a sash distance sensor (FH-DS, FH-DV)

nvoSwitchPos

Type: SNVT_count

Equipment function: FH


Function

  • Output of the current switching step of the fume cupboard as a numeric value if the fume cupboard controller is equipped with switch contacts for 2-point or 3-point control (FH-2P, FH-3P)

nvoPressAct

Type: SNVT_press_p, unit: Pa

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of the differential pressure actual value within the EASYLAB system
  • The actual value is recorded by a differential pressure transducer connected to the RR with RMF or to the TAM with RMF

nvoPressSet

Type: SNVT_press_p, unit: Pa

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of the differential pressure setpoint value within the EASYLAB system

nvoDampPos

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, RR with RMF


Function

  • Output of the damper blade position
  • Damper blade position 0 – 100 %

nvoLocalAlarm

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of a local alarm for a fume cupboard controller, extract air controller, supply air controller, room controller or TAM
  • Alarm conditions can be defined using the EasyConnect configuration software

nvoSummaryAlarm

Type: SNVT_switch

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of a consolidated alarm
  • An alarm signal is generated when a controller emits an alarm or fault message.
  • Alarm conditions can be defined using the EasyConnect configuration software
  • Standard configuration: volume flow rate alarm

nvoPressAlarm

Type: SNVT_switch

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of a room pressure alarm when room pressure control is active
  • Alarm conditions can be defined using the EasyConnect configuration software

nvoSystemDevices

Type: SNVT_count

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 2.0 and TCU3, TAM 3.0


Function

  • Number of identified EASYLAB system components

nvoStateDIO

Type: SNVT_state

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 2.0 and TCU3, TAM 3.0


Function

  • Bit string indicating the states of the switch inputs and outputs of the controller or adapter module

nvoSC_LockHP

Type: SNVT_switch


Function

  • Feedback, sash has been locked, high priority

nvoSC_GetPos

Type: SNVT_switch


Function

  • Sash status (open/closed)

nvoSC_Alarm

Type: SNVT_switch


Function

  • 'Automatic sash device not ready' signal

nvoDO_SetByLocal

Type: SNVT_state

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 4.0


Function

  • Feedback from digital outputs (relays) which are used by the control system and can hence not receive signals from external devices

nvoVoltageAI2

Type: SNVT_volt, unit V

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 4.0 and TCU3, TAM 7.0


Function

  • Output of the voltage at analogue input AI2
  • 0 – 10 V DC, in increments of 0.1 V

nvoVoltageAI3

Type: SNVT_volt, unit V

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 4.0 and TCU3, TAM 7.0


Function

  • Output of the voltage at analogue input AI3
  • 0 – 10 V DC, in increments of 0.1 V

Additional information for nvoDampMin_** and nvoDampMax_** functional values

nvoDampPosMax_** (State)

0 All damper blades in standard operating mode. Intervention is possible.

–1 All damper blades in OPEN mode (special operating mode, value = 100 %). Intervention is possible.

1 At least one damper blade in OPEN mode (special operating mode).

nvoDampPosMin_** (State)

0 All damper blades in standard operating mode. Intervention is possible.

–1 All damper blades in shut-off mode (special operating mode, value = 0 %). Intervention is not possible.

1 At least one damper blade in shut-off mode (special operating mode).

nvoDampPosMax_FH

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the fume cupboard controller with the widest open damper blade
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

nvoDampPosMin_FH

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the fume cupboard controller with the least wide open damper blade
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

nvoDampPosMax_RE

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the room extract air controller with the widest open damper blade
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

nvoDampPosMin_RE

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the room extract air controller with the least wide open damper blade
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

nvoDampPosMax_TE

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the fume cupboard or extract air or room extract air controller with the widest open damper blade
  • For the evaluation of the damper blade positions in the extract air system (1 fan) for fume cupboard, extract air and room extract air

nvoDampPosMin_TE

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the fume cupboard or extract air or room extract air controller with the least wide open damper blade
  • For the evaluation of the damper blade positions in the extract air system (1 fan) for fume cupboard, extract air and room extract air

nvoDampPosMax_RS

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the room supply air controller with the widest open damper blade

nvoDampPosMin_RS

Type: SNVT_switch

Equipment functions: FH, EC/SC, RR, TAM, RR with RMF, TAM with RMF


Function

  • Output of the damper blade position of the room supply air controller with the least wide open damper blade

nvoDampPosMax_EC

Type: SNVT_switch

Equipment functions: FH, EC, SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the extract air controller with the widest open damper blade
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard, extract air and room extract air

nvoDampPosMin_EC

Type: SNVT_switch

Equipment functions: FH, EC, SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the extract air controller with the least wide open damper blade
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard, extract air and room extract air

nvoDampPosMax_SC

Type: SNVT_switch

Equipment functions: FH, EC, SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the supply air controller with the widest open damper blade
  • For the evaluation of the damper blade positions in separate supply air systems (2 fans), i.e. supply air and room supply air

nvoDampPosMin_SC

Type: SNVT_switch

Equipment functions: FH, EC, SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the supply air controller with the least wide open damper blade
  • For the evaluation of the damper blade positions in separate supply air systems (2 fans), i.e. supply air and room supply air

nvoDampPosMax_TS

Type: SNVT_switch

Equipment functions: FH, EC, SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the room supply air or room extract air controller with the widest open damper blade
  • For the evaluation of the damper blade positions in supply air systems (1 fan) for supply air and room supply air

nvoDampPosMin_TS

Type: SNVT_switch

Equipment functions: FH, EC, SC, RR, TAM, RR with RMF, TAM with RMF

from firmware version EM-LON 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the room supply air or room extract air controller with the least open damper blade
  • For the evaluation of the damper blade positions in supply air systems (1 fan) for supply air and room supply air

OC_OCCUPIED

Function Bit
Function 0 1 2 3

Standard mode

0

0

0

0

Reduced operation

0

0

0

1

Increased operation

0

0

1

0

Shut-off mode

0

1

0

0

OPEN position

1

0

0

0


OC_UNOCCUPIED

Function Bit
Function 4 5 6 7

Standard mode

0

0

0

0

Reduced operation

0

0

0

1

Increased operation

0

0

1

0

Shut-off mode

0

1

0

0

OPEN position

1

0

0

0


OC_BYPASS

Function Bit
Function 8 9 10 11

Standard mode

0

0

0

0

Reduced operation

0

0

0

1

Increased operation

0

0

1

0

Shut-off mode

0

1

0

0

OPEN position

1

0

0

0


OC_STANDBY

Function Bit
Function 12 13 14 15

Standard mode

0

0

0

0

Reduced operation

0

0

0

1

Increased operation

0

0

1

0

Shut-off mode

0

1

0

0

OPEN position

1

0

0

0


Default values for nviManOverride

State Description

HVO_Position

Standard mode

HVO_Close

Shut-off mode

HVO_Open

OPEN position

HVO_Minimum

Reduced operation

HVO_Maximum

Increased operation

HVO_Nul

No default


Assignment of functional values to operating modes – basic configuration

Value Identifier Operating mode

0

OC_OCCUPIED

Standard mode

1

OC_UNOCCUPIED

Reduced operation

2

OC_BYPASS

Increased operation

3

OC_BYPASS

Shut-off mode

0xFF

OC_NUL

No default


Default values for nviMode

Bit Function 0 1

4/11

OPEN position

inactive

active

3/12

Shut-off mode

inactive

active

2/13

Increased operation

inactive

active

1/14

Reduced operation

inactive

active

0/15

Standard mode

inactive

active


Default settings for nviManOp_Disable

Value State Function

0

- Manual control has been enabled on the control panel - Operating mode defaults set on DI override LON

1

- Manual control has been disabled on the control panel - Operating mode default settings from LON have the highest priority


Default settings for nviVolOffset_T

Value State Function

Percentage value

External volume flow rate setpoint change for temperature: 0.0 – 100.0 %


Default settings for nviVolOffset_P

Value State Function

Percentage value

External volume flow rate setpoint change for differential pressure: 0.0 – 100.0 %


Default settings for nviPressSetSel

Value State Function

0

0

Differential pressure setpoint 1

100

1

Differential pressure setpoint 2


Default settings for nviSunblinder

Value State Description

0

0

Close blinds (activate switching output DO6)

100

1

Open blinds (activate switching output DO5)

0

-1

No default


Default values for nviDO_Set

Bit Function

7

DO1

6

DO2

5

DO3

4

DO4

3

DO5

2

DO6

0 inactive

1 active


nvoManOverride functional values

State Description

HVO_Position

Standard mode

HVO_Close

Shut-off mode

HVO_Open

OPEN position

HVO_Minimum

Reduced operation

HVO_Maximum

Increased operation


nvoManOverride_R functional values

State Description

HVO_Position

Standard mode

HVO_Close

Shut-off mode

HVO_Open

OPEN position

HVO_Minimum

Reduced operation

HVO_Maximum

Increased operation


nvoMode functional values

Bit Function 0 1

11

OPEN position

inactive

active

12

Shut-off mode

inactive

active

13

Increased operation

inactive

active

14

Reduced operation

inactive

active

15

Standard mode

inactive

active


nvoMode_R functional values

Bit Function 0 1

11

OPEN position

inactive

active

12

Shut-off mode

inactive

active

13

Increased operation

inactive

active

14

Reduced operation

inactive

active

15

Standard mode

inactive

active


nvoOccCmd functional values

Value Identifier Operating mode

0

OC_OCCUPIED

Standard mode

1

OC_UNOCCUPIED

Reduced operation

2

OC_BYPASS

Increased operation

3

OC_STANDBY

Shut-off mode


nvoOccCmd_R functional values (basic configuration)

Value Identifier Operating mode

0

OC_OCCUPIED

Standard mode

1

OC_UNOCCUPIED

Reduced operation

2

OC_BYPASS

Increased operation

3

OC_STANDBY

Shut-off mode


nvoSwitchPos functional values

Value Description

1

Switching step 1

2

Switching step 2

3

Switching step 3

0

invalid


nvoLocalAlarm functional values

Value State Description

0

0

Local alarm is inactive

100

1

Local alarm is active


nvoSummaryAlarm functional values

Value State Description

0

0

Consolidated alarm is inactive

100

1

Consolidated alarm is active


nvoPressAlarm functional values

Value State Description

0

0

Room pressure alarm inactive

100

1

Room pressure alarm active


Bit list

us16_varState_IO LonWorks bit

Switching state DO6

2

Switching state DO5

3

Switching state DO4

4

Switching state DO3

5

Switching state DO2

6

Switching state DO1

7

Switching state DI6

10

Switching state DI5

11

Switching state DI4

12

Switching state DI3

13

Switching state DI2

14

Switching state DI1

15


Default values for nvoDO_SetByLocal

Bit Function

7

DO1

6

DO2

5

DO3

4

DO4

3

DO5

2

DO6

0 inactive

1 active


nvoDampPosMax_FH functional values

Value State

Damper blade position

Additional information


nvoDampPosMin_FH functional values

Value State

Damper blade position

Additional information


nvoDampPosMax_RE functional values

Value State

Damper blade position

Additional information


nvoDampPosMin_RE functional values

Value State

Damper blade position

Additional information


nvoDampPosMax_TE functional values

Value State

Damper blade position

Additional information


nvoDampPosMin_TE functional values

Value State

Damper blade position

Additional information


nvoDampPosMax_RS functional values

Value State

Damper blade position

Additional information


nvoDampPosMin_RS functional values

Value State

Damper blade position

Additional information


nvoDampPosMax_EC functional values

Value State

Damper blade position

Additional information


nvoDampPosMin_EC functional values

Value State

Damper blade position

Additional information


nvoDampPosMax_SC functional values

Value State

Damper blade position

Additional information


nvoDampPosMin_SC functional values

Value State

Damper blade position

Additional information


nvoDampPosMax_TS functional values

Value State

Damper blade position

Additional information


nvoDampPosMin_TS functional values

Value State

Damper blade position

Additional information


Installation details

  • Installation details

Installation and commissioning

Installation

  • As attachment for the EASYLAB base component: factory mounted
  • For retrofitting: Mount the expansion module into the base casing
  • Connect to the LonWorks network


Commissioning

  • The EASYLAB controller identifies the expansion module automatically
  • Integrate system with the LonWorks network and link the data points logically (binding) using a network management tool (e.g. Echelon LonMarker, to be provided by others)
  • Load EASYLAB LonWorks application
  • Applications are available for download from our website

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.


Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request.
Tel.: +971 4 3417448 | Fax: +971 4 3417449

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +971 4 3417448 | Fax: +971 4 3417449

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request.
Tel.: +971 4 3417448 | Fax: +971 4 3417449

Attachment (max. 10MB)

Fields marked with an (*) are required fields.