Functional description
Displacement flow diffusers discharge the air from air conditioning systems with a low velocity and near the floor. The low-turbulence airflow moves along the wall and towards the floor, where it eventually covers the entire floor area. The convection from people and other heat sources causes the fresh air from the pool to rise and create comfortable conditions in the occupied zone.
Displacement ventilation is characterised by low airflow velocities and low turbulence. The air quality in the occupied zone is very high.
Displacement ventilation with air discharge near the floor is suitable only for cooling. The maximum supply air to room air temperature difference is –6 K.
Type QLW-AZ displacement flow diffusers include an equalising element which distributes the supply air flow equally across the entire diffuser area. The perforated sheet metal diffuser face helps to equalise the airflow further. One-way air discharge.
The upper part of the diffuser face is used for extract air. This solution is ideal insofar as the extract air has to be removed above the occupied zone.
Nominal sizes | 600, 750, 900, 1050, 1200 mm |
Minimum volume flow rate, at approx. 0.2 m/s | 12 – 25 l/s or 43 – 90 m³/h |
Maximum volume flow rate, at approx. 0.4 m/s | 25 – 45 l/s or 90 – 162 m³/h |
Supply air to room air temperature difference | –6 to –1 K |
Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures.
QLW-AZ, sound power level and total differential pressure
600 | 12 | 43 | 0.18 | 7 | <3 | <15 | 9 | 3 | <15 | 16 | 10 | 17 |
600 | 15 | 54 | 0.23 | 11 | 3 | 19 | 13 | 5 | 21 | 26 | 15 | 24 |
600 | 20 | 72 | 0.30 | 19 | 5 | 31 | 24 | 10 | 32 | 46 | 27 | 34 |
600 | 25 | 90 | 0.38 | 30 | 7 | 40 | 37 | 15 | 41 | 72 | 42 | 42 |
750 | 15 | 54 | 0.18 | 8 | <3 | 16 | 10 | 6 | 19 | 24 | 16 | 21 |
750 | 20 | 72 | 0.24 | 14 | 4 | 26 | 18 | 10 | 29 | 42 | 28 | 31 |
750 | 25 | 90 | 0.30 | 21 | 6 | 34 | 28 | 16 | 37 | 65 | 43 | 39 |
750 | 30 | 108 | 0.36 | 31 | 9 | 41 | 41 | 24 | 43 | 94 | 63 | 45 |
900 | 20 | 72 | 0.20 | 11 | 4 | 24 | 16 | 9 | 27 | 38 | 28 | 29 |
900 | 25 | 90 | 0.25 | 17 | 6 | 31 | 25 | 15 | 35 | 59 | 44 | 36 |
900 | 30 | 108 | 0.30 | 24 | 9 | 37 | 36 | 21 | 41 | 85 | 63 | 43 |
900 | 35 | 126 | 0.35 | 33 | 12 | 42 | 49 | 29 | 46 | 116 | 86 | 48 |
1050 | 20 | 72 | 0.17 | 10 | 4 | 23 | 16 | 10 | 28 | 37 | 29 | 31 |
1050 | 25 | 90 | 0.22 | 15 | 6 | 30 | 25 | 15 | 36 | 58 | 45 | 38 |
1050 | 30 | 108 | 0.26 | 22 | 8 | 36 | 36 | 22 | 41 | 84 | 65 | 43 |
1050 | 40 | 144 | 0.35 | 39 | 15 | 45 | 64 | 39 | 51 | 149 | 116 | 52 |
1200 | 25 | 90 | 0.19 | 13 | 5 | 29 | 20 | 15 | 34 | 58 | 43 | 39 |
1200 | 30 | 108 | 0.23 | 19 | 8 | 35 | 29 | 22 | 40 | 84 | 61 | 44 |
1200 | 35 | 126 | 0.27 | 25 | 10 | 39 | 40 | 30 | 45 | 114 | 83 | 48 |
1200 | 45 | 162 | 0.34 | 42 | 17 | 46 | 66 | 49 | 52 | 189 | 138 | 55 |
① Supply air
② Extract air
QLW-AZ-ZT, sound power level and total differential pressure
600 | 7 | 25 | 0.11 | 5 | 3 | <15 | 5 | 4 | <15 | 7 | 6 | <15 |
600 | 10 | 36 | 0.15 | 10 | 7 | 15 | 10 | 8 | 17 | 14 | 11 | 19 |
600 | 15 | 54 | 0.23 | 22 | 15 | 28 | 22 | 17 | 30 | 31 | 26 | 31 |
600 | 20 | 72 | 0.30 | 40 | 27 | 38 | 40 | 31 | 39 | 54 | 46 | 40 |
750 | 10 | 36 | 0.12 | 9 | 6 | 15 | 9 | 7 | 15 | 13 | 10 | 20 |
750 | 15 | 54 | 0.18 | 20 | 15 | 28 | 20 | 15 | 28 | 29 | 22 | 32 |
750 | 20 | 72 | 0.24 | 35 | 26 | 36 | 35 | 27 | 37 | 51 | 39 | 40 |
750 | 25 | 90 | 0.30 | 55 | 41 | 43 | 55 | 42 | 44 | 79 | 61 | 47 |
900 | 15 | 54 | 0.15 | 18 | 14 | 26 | 19 | 16 | 28 | 26 | 16 | 30 |
900 | 20 | 72 | 0.20 | 32 | 25 | 35 | 33 | 29 | 37 | 47 | 29 | 38 |
900 | 25 | 90 | 0.25 | 50 | 40 | 41 | 52 | 46 | 43 | 73 | 46 | 44 |
900 | 30 | 108 | 0.30 | 73 | 57 | 46 | 75 | 66 | 49 | 106 | 66 | 49 |
1050 | 20 | 72 | 0.17 | 32 | 25 | 35 | 33 | 31 | 38 | 47 | 46 | 40 |
1050 | 25 | 90 | 0.22 | 50 | 39 | 42 | 52 | 49 | 44 | 74 | 72 | 46 |
1050 | 30 | 108 | 0.26 | 73 | 56 | 47 | 74 | 70 | 50 | 106 | 103 | 51 |
1050 | 35 | 126 | 0.30 | 99 | 77 | 52 | 101 | 95 | 54 | 145 | 141 | 55 |
1200 | 25 | 90 | 0.19 | 50 | 37 | 42 | 51 | 46 | 43 | 76 | 68 | 45 |
1200 | 30 | 108 | 0.23 | 73 | 54 | 47 | 74 | 66 | 48 | 109 | 98 | 50 |
1200 | 35 | 126 | 0.27 | 99 | 73 | 51 | 101 | 90 | 53 | 149 | 134 | 55 |
1200 | 40 | 144 | 0.30 | 129 | 96 | 55 | 132 | 117 | 57 | 194 | 175 | 59 |
① Supply air
② Extract air
Displacement flow diffusers as supply and extract air combinations, suitable for comfort zones with special demands on architecture and design.
With one-way air discharge for low-turbulence displacement ventilation. For wall and bulkhead installation.
Ready-to-install component which consists of a casing with horizontal spigots, an equalising element, and a perforated sheet metal diffuser face.
Spigot suitable for ducts to EN 1506 or EN 13180.
Sound power level of the air-regenerated noise measured according to EN ISO 5135.
Special characteristics
Materials and surfaces
Mineral wool
Technical data
Sizing data
Air-regenerated noise
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
|
|
Order example: QLW-AZ–ZT/750/P1-RAL 9016
Cross-talk attenuator | With |
Damper blade for volume flow rate balancing | Without |
Lip seal | Without |
Nominal size | 750 mm |
Exposed surface | RAL 9016, traffic white, gloss level 70 % |
Installation and commissioning
These are only schematic diagrams to illustrate installation details.
Principal dimensions
B₁ [mm]
Width of diffuser face
B₄ [mm]
Width of a rectangular spigot
ØD [mm]
Outer diameter of the spigot
ØD₁ [mm]
Casing diameter
H₁ [mm]
Height of diffuser face
T₁ [mm]
Casing depth
T₄ [mm]
Depth of a rectangular spigot
m [kg]
Weight
Nomenclature
LWA [dB(A)]
A-weighted sound power level of air-regenerated noise
V [m³/h] and [l/s]
Volume flow rate
v0 [m/s]
Theoretical airflow velocity across the diffuser area, at a distance of 0 m from the diffuser face
Lnz [m]
Near zone of the displacement flow diffuser, where the comfort criteria may not be achieved
The near zone is at least 0.5 m, independent of the airflow velocity
At distance Lnz the airflow velocity is 0.2 m/s max., measured 0.1 m above the floor
Δtz [K]
Supply air to room air temperature difference, i.e. supply air temperature minus room temperature
Δpt [Pa]
Total differential pressure
Aeff [m²]
Effective air discharge area
All sound power levels are based on 1 pW.
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +971 4 3417448 | Fax: +971 4 3417449
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +971 4 3417448 | Fax: +971 4 3417449
Contact
We are here for you
Please specify your message and type of request.
Tel.: +971 4 3417448 | Fax: +971 4 3417449
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +971 4 3417448 | Fax: +971 4 3417449