00131938_0
Shut-off damper, variant AK, with actuator


00131938_0
00132715_0
00132820_0

AK 

For low-leakage shut-off

Circular shut-off dampers for shutting off volume flows in ventilation ducts of air conditioning systems

  • Maintenance-free damper blade mechanism
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing air leakage to EN 1751, class C

Optional equipment and accessories

  • Electric actuator
  • Spring return actuator
  • Pneumatic actuator
  • Auxiliary switch with adjustable switching points for capturing the end positions

General information

Application

  • Circular shut-off dampers Type AK for shutting off or restricting the airflow in ventilation ducts of air conditioning systems

Special features

  • Damper blade can be actuated manually, electrically or pneumatically
  • Low-leakage shut-off
  • Safety function provided by optional spring return actuator

Nominal sizes

  • 100, 125, 160, 200, 250, 315, 400


Variants

  • AK: Shut-off damper
  • AK-FL: Shut-off damper with flanges on both ends

Construction

  • Galvanised sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)
  • A2: Stainless steel

Parts and characteristics

  • Ready-to-install shut-off damper
  • Damper blade with blade mechanism

Attachments

  • Open/Close actuators: For the opening and closing of shut-off dampers in air conditioning systems
  • Auxiliary switch for capturing the end positions

Accessories

  • Lip seals on both ends (factory fitted)
  • Matching flanges for both ends


Materials and surfaces

Galvanised sheet steel construction

  • Casing and damper blade made of galvanised sheet steel
  • Blade seal made of TPE plastic
  • Bearings made of TPU


Powder-coated construction (P1)

  • Casing made of galvanised sheet steel, powder-coated
  • Damper blade made of stainless steel 1.4301
  • Shaft made of stainless steel 1.4305


Stainless steel construction (A2)

  • Casing and damper blade made of stainless steel 1.4301
  • Shaft made of stainless steel 1.4305

Standards and guidelines

  • Meets the hygiene requirements of VDI 6022
  • Closed blade air leakage to EN 1751, class 4 (nominal sizes 100, 125 and 160, class 3)
  • Nominal sizes 100, 125, and 160 meet the general requirements, nominal sizes 200 – 400 meet the increased requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage
  • Casing air leakage to EN 1751, class C

Maintenance

  • Maintenance-free, as construction and materials are not subject to wear and tear

Technical information

  • Function
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE
AK: schematic representation 00137312_0
① Damper blade
② Lip seal
③ Casing
④ Actuator


Functional description

For airtight shut-off of volume flows in round air ducts. The basic version is shut off by manually actuating the damper blade. Electrically or pneumatically operated actuators, which are available in different versions, can also be used to operate the damper blade. The versions differ with regard to the power supply and safety position (de-energised or de-pressurised state). Actuators with auxiliary switches for electrical monitoring of the damper blade position are also available.

The actuator of a damper blade must be controlled by a customer-side circuit and then moves the damper blade to the OPEN or CLOSED position.

Downloads

product information

certificates

operation manuals

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"1; mode=block", "x-content-type-options"=>"nosniff", "x-download-options"=>"noopen", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +971 4 3417448 | Fax: +971 4 3417449

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +971 4 3417448 | Fax: +971 4 3417449

Contact

We are here for you

Please specify your message and type of request.
Tel.: +971 4 3417448 | Fax: +971 4 3417449

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +971 4 3417448 | Fax: +971 4 3417449